Huddersfield power station supplied electricity to the town of Huddersfield and the wider area from 1893 to 1981. It was owned and operated by Huddersfield Corporation until the nationalisation of the electricity supply industry in 1948. The power station was redeveloped several times: including the incorporation of new plant in the 1910s, and in the 1930s to 1950s. The station was decommissioned in October 1981.
Huddersfield power station | |
---|---|
Country | England |
Location | Huddersfield West Yorkshire |
Coordinates | 53°39′11″N 01°46′27″W / 53.65306°N 1.77417°W |
Status | Decommissioned and demolished |
Construction began | 1891 |
Commission date | 1893 |
Decommission date | 1981 |
Owner(s) | Huddersfield Corporation (1893–1948) British Electricity Authority (1948–1955) Central Electricity Authority (1955–1957) Central Electricity Generating Board (1958–1981) |
Operator(s) | As owner |
Thermal power station | |
Primary fuel | Coal |
Turbine technology | Steam turbines |
Chimneys | 1 |
Cooling towers | 3 |
Cooling source | Cooling towers |
Power generation | |
Units operational | 2 x 20 MW, 2 x 30 MW (after 1955) |
Make and model | English Electric 20 MW, GEC 30 MW |
Nameplate capacity | 100 MW installed, output 94 MW |
Annual net output | 417 GWh (1962) |
Another power station, together with car sheds and offices, was located at Longroyd Bridge which supplied the Huddersfield tram system with electricity from 1901 to 1940.
In 1890 Huddersfield Corporation applied for a Provisional Order under the Electric Lighting Acts to generate and supply electricity to the town. This was granted by the Board of Trade and was confirmed by Parliament through the Electric Lighting Orders Confirmation (No. 3) Act 1890 (53 & 54 Vict. c. clxxxviii).[1] The power station was built in St. Andrew’s Road (53°39'11"N 1°46'27"W) and first supplied electricity on 29 June 1893.[2]
The original plant at Huddersfield power station comprised vertical condensing engines coupled directly and by ropes to Ferranti and Mordey dynamos. In 1898 the generating capacity was 1,150 kW and the maximum load was 636 kW.[2]
Following the First World War new plant was installed to meet growing demand for electricity. By 1923 the generating plant comprised:[3]
These machines gave a total generating capacity of 17,300 kW of alternating current.[3]
A variety of electricity supplies were available to consumers as:
In the early 1920s the Halifax and Huddersfield electricity undertakings interconnected their systems with an underground cable to share supplies. This facility was constructed at considerable cost rather than taking a supply from the Yorkshire Power Company, even though it was offered at a price less than their own costs of generation.[4]
New plant was commissioned over the extended period of 1938–1955.[5]
The boilers had a total evaporative capacity of 1,200,000 lb/h (151.2 kg/s), and supplied steam to:
The completed total installed generating capacity was 100 MW, with an output capacity 64 MW.[5] The generating sets were commissioned over an extended period: November 1938, November 1946, December 1953, and July 1955.
Operational data for the early years of operation was as follows:[2]
Year | Consumers | Lamps | Electricity sold MWh |
---|---|---|---|
1893 | 112 | 9,613 | 43.2 |
1894 | 214 | 15,342 | 156.2 |
1895 | 280 | 28,983 | 227.8 |
1896 | 385 | 28,983 | 304.2 |
1897 | 598 | 41,702 | 438.8 |
1898 | ? | 43,309 | 379.8 |
The growth in number of consumers, lamps and current sold is evident.
In 1898 maximum electricity demand was 375 kW.[2]
The operating data for the period 1921–23 is shown in the table:[3]
Electricity Use | Units | Year | ||
---|---|---|---|---|
1921 | 1922 | 1923 | ||
Lighting and domestic use | MWh | 2,816.50 | 2,242.24 | 3,029.49 |
Public lighting use | MWh | 84.99 | 98.74 | 113.94 |
Traction | MWh | – | – | 1,919.68 |
Power use | MWh | 14,166.96 | 11,072.66 | 12,991.78 |
Total use | MWh | 17,068.44 | 14,013.64 | 18,054.87 |
Load and connected load | ||||
Maximum load | kW | 7245 | 7870 | 9060 |
Total connections | kW | 30,515 | 33,250 | 34,889 |
Load factor | Per cent | 33.9 | 28.2 | 30.2 |
Financial | ||||
Revenue from sales of current | £ | – | 193,516 | 180,870 |
Surplus of revenue over expenses | £ | – | 40,703 | 62,771 |
The growth of demand and use of electricity is evident.
Under the terms of the Electricity (Supply) Act 1926 (16-17 Geo. 5 c. 51)[7] the Central Electricity Board (CEB) was established in 1926.[8] The CEB identified high efficiency ‘selected’ power stations that would supply electricity most effectively; Huddersfield was designated a selected station. The CEB also constructed the national grid (1927–33) to connect power stations within a region.[8]
Huddersfield power station operating data, 1946 is given in the table:[9]
Year | Load factor per cent | Max output load MW | Electricity supplied GWh | Thermal efficiency per cent |
---|---|---|---|---|
1946 | 41.9 | 50,650 | 184.776 | – |
The British electricity supply industry was nationalised in 1948 under the provisions of the Electricity Act 1947 (10-11 Geo. 6 c. 54).[10] The Huddersfield electricity undertaking was abolished, ownership of Huddersfield power station was vested in the British Electricity Authority, and subsequently the Central Electricity Authority and the Central Electricity Generating Board (CEGB).[8] At the same time the electricity distribution and sales responsibilities of the Huddersfield electricity undertaking were transferred to the Yorkshire Electricity Board (YEB).
Operating data for the period 1954–79 is shown in the table:[5][11][12][13]
Year | Running hours or load factor (per cent) | Maximum output capacity MW | Electricity supplied GWh | Thermal efficiency per cent |
---|---|---|---|---|
Low pressure plant (English Electric 20 MW turbo-alternators) | ||||
1954 | 8582 | 38 | 249.157 | 22.13 |
1955 | 6494 | 38 | 161.504 | 21.04 |
1956 | 5137 | 38 | 118.395 | 20.28 |
1957 | 3218 | 38 | 43.803 | 19.02 |
1958 | 3582 | 38 | 60.023 | 18.85 |
High pressure plant (GEC 30 MW turbo-alternators) | ||||
1955 | 7849 | 28 | 196.256 | 25.96 |
1956 | 8557 | 56 | 278.583 | 25.65 |
1957 | 8080 | 56 | 372.432 | 24.71 |
1958 | 7582 | 56 | 352.781 | 25.46 |
Combined plant | ||||
1961 | 42.4 % | 94 | 349.068 | 22.60 |
1962 | 50.6 % | 94 | 416.718 | 22.69 |
1963 | 44.9 % | 94 | 369.670 | 22.50 |
1967 | 44.7 % | 94 | 368.187 | 22.94 |
1972 | 30.3 % | 94 | 249.934 | 21.18 |
1979 | 16.3 % | 56 | 80.030 | 20.83 |
The less intensive use of the ‘low pressure’ plant over the period 1954-8 and the increasing use of the high pressure plant 1955–63 is evident, until its usage also declined in the 1970s.
Huddersfield power station was decommissioned on 26 October 1981.[14] The buildings subsequently demolished and the area has been redeveloped with industrial and commercial units.